The Shifa emergency generator capacity is 650 kVA (refer attachment) At full load the gensets would run for 2.56 hours on 300L of diesel. The hospital however would be at level RED, essential loads only, so 300 Litres being sufficient for only 30 minutes of power is incorrect. https://www.researchgate.net/publication/308809924_Energy_management_systems_for_hospitals_in_Gaza-strip/link/58047a0908ae6c2449f96762/download
Written by 0DE1677594336F4EF0A27B9232264220AA4B578E599BC5045FA8BAED925FB586
Participant Details
Original Tweet
Tweet embedding is no longer reliably available, due to the platform's instability (in terms of both technology and policy). If the Tweet still exists, you can view it here: https://twitter.com/foo_bar/status/1723945312396497254
Please note, though, that you may need to have your own Twitter account to access that page. I am currently exploring options for archiving Tweet data in a post-API context.
All Information
- ID - 1724038745186504734
- noteId - 1724038745186504734
- participantId -
- noteAuthorParticipantId - 0DE1677594336F4EF0A27B9232264220AA4B578E599BC5045FA8BAED925FB586 Participant Details
- createdAtMillis - 1699877842600
- tweetId - 1723945312396497254
- classification - MISINFORMED_OR_POTENTIALLY_MISLEADING
- believable -
- harmful -
- validationDifficulty -
- misleadingOther - 0
- misleadingFactualError - 1
- misleadingManipulatedMedia - 0
- misleadingOutdatedInformation - 0
- misleadingMissingImportantContext - 0
- misleadingUnverifiedClaimAsFact - 1
- misleadingSatire - 0
- notMisleadingOther - 0
- notMisleadingFactuallyCorrect - 0
- notMisleadingOutdatedButNotWhenWritten - 0
- notMisleadingClearlySatire - 0
- notMisleadingPersonalOpinion - 0
- trustworthySources - 1
- summary
- The Shifa emergency generator capacity is 650 kVA (refer attachment) At full load the gensets would run for 2.56 hours on 300L of diesel. The hospital however would be at level RED, essential loads only, so 300 Litres being sufficient for only 30 minutes of power is incorrect. https://www.researchgate.net/publication/308809924_Energy_management_systems_for_hospitals_in_Gaza-strip/link/58047a0908ae6c2449f96762/download
Note Status History
createdAt | timestampMillisOfFirstNonNMRStatus | firstNonNMRStatus | timestampMillisOfCurrentStatus | currentStatus | timestampMillisOfLatestNonNMRStatus | mostRecentNonNMRStatus | participantId |
2023-11-13 12:17:22 UTC (1699877842600) |
1969-12-31 23:59:59 UTC (-1) |
2023-11-14 04:08:18 UTC (1699934898456) |
NEEDS_MORE_RATINGS | 1969-12-31 23:59:59 UTC (-1) |
Note Ratings
rated at | rated by | |
2023-11-13 08:12:02 -0600 | Rating Details | |
2023-11-13 06:39:04 -0600 | Rating Details |